-40%
Honeywell Pressuretrol L404F 1060
$ 17.29
- Description
- Size Guide
Description
Honeywell Pressuretrol L404F 1060. Condition is "Used". I pulled it off my boiler after the boiler rusted through and this part had been replaced more recently.. please let me know any questions before you purchase it.Shipped with USPS Priority Mail.
Features:
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element.
Models have snap-acting switching to open or close a circuit on pressure rise.
Have adjustable differentials.
Adjustments are made by screws on top of case.
Mount using 1/4 inch -18 NPT internal pipe threads or surface mount through base of case.
Ground screw terminal.
Product Specifications:
Application: Provide control of steam, air, non-combustible gases or non-corrosive fluids
Dimensions (in.): 4-27/32 in. high x 4-1/2 in. wide x 3-1/4 in. deep
Dimensions (mm): 123 mm high x 114 mm wide x 83 mm deep
Mounting: 1/4 in. NPT internal thread or surface mount through back of case
Approvals, Underwriters Laboratories Inc: Listed: File No. MP466, Guide No. MBPR
Approvals, CSA: Certified: File No. LR1620, Guide No. 400-E-O
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact-- 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac Switch Contact-- 5.1 AFL, 30.6 ALR, 5.0 A resistive
Operating Temperature Range (F): -35 F to +150 F
Operating Temperature Range (C): -37 C to +66 C
Approvals, Swiss RE: Acceptable
Sensor Element: Stainless Steel diaphragm
Operating Range (psi): 2 to 15 psi; 25 psi - Maximum Sustained
Operating Range (kPa): 14 to 103 kPa; 172 kPa - Maximum Sustained
Differential Pressure Range (psi): 2 to 6 psi
Differential Pressure Range (kPa): 14 to 41 kPa
Differential Type: Subtractive
Switch Operation: Auto recycle
Switching Action: SPDT snap action, make R-W, break R-B on pressure rise
Pipe Connection: Main or High Pressure--1/4 in. NPT internal thread
Shipped with USPS Priority Mail Padded Flat Rate Envelope.